An energy model of a building produces one set of results: how much electricity, gas and other fuels the building uses each hour. Yet the same model can show a 20% improvement under one programme and only 10% under another. The difference is the metric. Site energy, source energy, energy cost and carbon each weigh fuels differently, and each programme picks one.
Site energy
Site energy is the energy delivered to the building and measured at its meters. A kilowatt-hour of electricity and a kilowatt-hour of gas count the same. It is simple and easy to verify against bills, which is why it is used for energy use intensity (EUI) in many disclosure reports and in some code calculations.
Its weakness is that it ignores what happens before the meter. Electricity is generated, often from fuel, with large losses in generation and transmission. Site energy treats electricity as if it had no such losses.
Source energy
Source energy adds the energy used to produce and deliver each fuel, using a conversion factor for each one. In the US, ENERGY STAR Portfolio Manager uses a factor of about 2.8 for grid electricity and close to 1.0 for natural gas. A kilowatt-hour of electricity therefore counts nearly three times as much as a kilowatt-hour of gas. The ENERGY STAR score and the source EUI used in many benchmarking ordinances are based on source energy.
Energy cost
Energy cost weighs each fuel by its price, including demand charges where the tariff has them. Electricity usually costs more per unit of energy than gas, so cost weighting also favours gas, though by an amount that depends on local rates. Energy cost is the metric used in ASHRAE 90.1 Appendix G for code compliance, in the 179D tax deduction, and in LEED v4. The baseline and proposed models must use the same rates.
Carbon
Greenhouse gas emissions weigh each fuel by the emissions it causes, using emission factors for each fuel and, for electricity, for the local grid. As grids add renewable power, the carbon factor of electricity falls, while gas stays largely constant. Carbon is the basis of NYC Local Law 97 and of many newer building performance standards. LEED v4.1 gives equal weight to energy cost and greenhouse gas emissions, and later versions of LEED put more weight on carbon.
Why the choice changes the answer
Take a design that replaces a gas boiler with an electric heat pump. Total site energy falls a great deal, because the heat pump delivers several units of heat for each unit of electricity. On source energy, part of that gain is lost, because each electric kilowatt-hour now counts nearly three times. On cost, the result depends on the electricity and gas rates. On carbon, the result depends on the grid, and improves every year the grid gets cleaner.
The reverse also happens. A design that saves electricity but adds gas use can look good on cost and source energy and poor on carbon. A measure is never simply "good" or "bad". It is good or bad on a given metric.
Which programme uses which
- ASHRAE 90.1 Appendix G (code compliance) — energy cost.
- LEED v4 — energy cost. LEED v4.1 — energy cost and greenhouse gas emissions together. LEED v5 — see our LEED v5 modeling guide.
- 179D — energy and power cost.
- ENERGY STAR and most benchmarking — source energy.
- Building performance standards — carbon (as in NYC LL97), or site or source EUI, or both, as in ASHRAE Standard 100.
- Some code checks — site energy, for example certain energy use limits within local codes.
Programmes also differ in edition, factors and rates, so always confirm the exact method for the project.
What this means for modelling
Agree the metric before modelling starts, and report the others alongside it. Design teams often want to know the carbon result even when compliance is judged on cost. When a project must meet two programmes, such as LEED and a local code, check early whether the same design passes both metrics. A design that sits close to a target on one metric may fall short on another.
The takeaway
The building does not change between metrics. The weighting of its fuels does. Know which metric your compliance path uses, report the others for context, and expect electrification measures in particular to look very different on site energy, source energy, cost and carbon.
Need savings reported on the right metric?
We build energy models for ASHRAE 90.1, LEED, 179D, NYC and building performance standard compliance, and report results on the metric each one uses. Let's talk.
Get in touchThis article is general guidance and reflects information available at the time of writing. Metrics, conversion factors and emission factors are defined by each programme and are updated from time to time — always use the values required by the programme and edition that apply to your project.