Every building has to bring in outdoor air for its occupants and send the same amount of stale air out. In winter, the outgoing air is warm and the incoming air is cold. In a humid summer, the outgoing air is cool and dry and the incoming air is hot and damp. Energy recovery uses the exhaust air to pre-condition the incoming air, so the HVAC system has less to do. The two main types are the HRV and the ERV.
HRV: heat only
A heat recovery ventilator (HRV) transfers sensible heat, meaning temperature only, between the two airstreams. The airstreams pass on opposite sides of thin plates, usually in a cross-flow or counter-flow core, without mixing. No moisture is exchanged. HRVs are common in cold, dry climates and in homes and buildings where indoor humidity is not a concern.
ERV: heat and moisture
An energy recovery ventilator (ERV) transfers both sensible heat and latent energy, meaning moisture. In summer it removes part of the humidity from the incoming air before it reaches the cooling coil. In winter it returns some indoor moisture to the dry incoming air. Two technologies are common:
- Enthalpy wheels — a slowly rotating wheel with a desiccant coating passes through both airstreams, picking up heat and moisture from one and releasing them into the other. Wheels reach high effectiveness and are common in larger commercial systems. A small amount of exhaust air can carry over to the supply side, which matters for some exhaust sources.
- Membrane cores — fixed plates made of a material that lets water vapour pass but not air. They have no moving parts and are common in smaller and residential units.
Which one to choose
- Hot and humid climates — an ERV, because removing moisture from outdoor air is a large part of the cooling load. See how ventilation rates are set in ASHRAE 62.1.
- Cold and dry climates — either. An HRV recovers heat well. An ERV also helps keep indoor humidity from falling too low in winter.
- Exhaust with moisture or odours — pools, kitchens and some laboratories often need an HRV or a run-around coil, so moisture or contaminants are not returned to the supply.
Effectiveness
Performance is stated as effectiveness: the share of the maximum possible heat or moisture transfer that the device achieves. Sensible effectiveness of roughly 60% to 80% is typical for good equipment. ERVs also have a latent effectiveness, which is usually lower. Effectiveness changes with airflow, so use the manufacturer's certified data at the design airflow, not a headline figure.
Frost control and bypass
In very cold weather, moisture in the exhaust air can freeze in the core or wheel. Frost control, such as preheating the outdoor air, slowing the wheel or briefly recirculating, protects the device but reduces recovery during the coldest hours. On mild days the opposite problem occurs: the building may want cool outdoor air for free cooling, and recovery would warm it. A bypass or wheel speed control lets the system skip recovery when it does not help. Both need to be included in the energy model, or the savings will be overstated.
Fan energy
A wheel or core adds pressure drop on both airstreams, so the fans use more energy all year. Recovery pays back when the temperature and humidity difference between indoor and outdoor air is large and the operating hours are long. In mild climates or buildings with short hours, the extra fan energy can cancel much of the saving. This is one reason codes require energy recovery only above certain thresholds.
Code requirements
ASHRAE 90.1 requires energy recovery on many systems, depending on the climate zone, the design supply airflow and the share of outdoor air, with separate thresholds for systems that run more than 8,000 hours a year. Recent editions require a minimum enthalpy recovery ratio of 50%. In an Appendix G model, the baseline includes energy recovery where the standard would require it, so a proposed ERV earns credit only for performance beyond that.
Energy recovery with a DOAS
A dedicated outdoor air system (DOAS) treats all of the outdoor air in a separate unit and delivers it to the spaces, while fan coils, VRF or chilled beams handle the room loads. Because a DOAS handles 100% outdoor air, energy recovery has the greatest effect there, and an ERV in the DOAS unit is standard practice in humid climates. Combined with demand-controlled ventilation, it gives tight control of both ventilation and humidity.
The takeaway
An HRV recovers heat. An ERV recovers heat and moisture. Choose by climate and by what is in the exhaust air, check effectiveness at design airflow, and model frost control, bypass and fan energy honestly. Where a DOAS is used, energy recovery is usually the most valuable part of it.