All articles
ASHRAE 62.1 · Ventilation · ·8 min read

ASHRAE 62.1 Ventilation Rate Procedure: How Outdoor Air Is Calculated

ASHRAE 62.1 ventilation rate procedure outdoor air calculation
Outdoor air is the most expensive air in the building. Calculate it; do not guess it.

Every commercial building has to bring in outdoor air, and every cubic foot of it must be heated, cooled and often dehumidified. Too little and air quality suffers. Too much and energy use climbs. ASHRAE Standard 62.1 sets the minimum, and its Ventilation Rate Procedure (VRP) is the calculation most designers and codes use.

Step 1: breathing zone outdoor air

The VRP treats each zone as having two sources of contaminants: the people, and the building itself. The outdoor air needed in the breathing zone is therefore the sum of two terms:

Breathing zone outdoor air = (people rate × number of people) + (area rate × floor area)

The rates come from a table by space type. For office space the people rate is 5 cfm per person and the area rate is 0.06 cfm per square foot. A 1,000 ft² office with five people needs 5 × 5 + 0.06 × 1,000 = 85 cfm in the breathing zone. Where the actual occupancy is unknown, the table gives a default density.

Step 2: air distribution effectiveness

Not all supply air reaches the people. The standard corrects for this with the zone air distribution effectiveness. A ceiling supply delivering cool air has an effectiveness of 1.0. A ceiling supply delivering warm air with a ceiling return can short-circuit, and its effectiveness drops to 0.8. Displacement and underfloor systems can score higher. The zone outdoor airflow is the breathing zone value divided by this effectiveness.

Step 3: the system level

What happens next depends on the system type.

System ventilation efficiency

For multiple-zone systems the standard uses two more ideas. Occupant diversity recognises that not every zone is at peak occupancy at once, so the people term is reduced. System ventilation efficiency accounts for the over-ventilation described above: the lower the efficiency, the more outdoor air the system must take in. It can be found by a simplified method or by a detailed calculation zone by zone.

The critical zone is usually one with many people and low supply airflow, such as a conference room on a VAV box turned down to minimum. Raising that box's minimum airflow, or giving the room its own system, often lowers the outdoor air for the whole air handler.

Other procedures in the standard

The VRP is not the only route. The Indoor Air Quality Procedure is a performance method based on contaminant concentrations, and the Natural Ventilation Procedure sets rules for openings and floor depth. Most projects use the VRP because codes and reviewers accept it without argument.

Demand-controlled ventilation

Spaces that are often partly empty, such as meeting rooms and auditoria, can reduce outdoor air when occupancy falls, usually with CO₂ sensors or occupancy sensors. Energy codes require this in many densely occupied spaces. The area term still applies when the space is empty but in use.

Where it meets LEED and energy modeling

LEED's minimum indoor air quality prerequisite is based on meeting Standard 62.1, and indoor environmental quality credits build on it. In an Appendix G energy model, baseline and proposed ventilation rates are generally the same, so the VRP result is an input to both. An error in the ventilation calculation moves both models and can also cause unmet load hours.

The takeaway

The Ventilation Rate Procedure is simple arithmetic applied carefully: people plus area, corrected for how well the air is delivered, then rolled up to the system. Most of the skill lies in the multiple-zone step, where one critical zone can set the outdoor air for an entire air handler.

Need ventilation calculations for LEED or permit?

We prepare ASHRAE 62.1 ventilation calculations, LEED indoor air quality documentation and the matching energy model inputs. Let's talk.

Get in touch

This article is general guidance and reflects information available at the time of writing. Ventilation rates and procedures are defined by the edition of ASHRAE 62.1 and the mechanical code adopted in your jurisdiction.