Prescriptive fire codes give fixed rules: travel distances, compartment sizes, numbers of exits. Many modern buildings cannot follow all of them. Atria, large open floors and long car parks need a performance-based approach, where the fire engineer shows by analysis that occupants can leave before conditions become dangerous. Two terms sit at the centre of that analysis: ASET and RSET.
The basic comparison
- ASET, available safe egress time — the time from ignition until conditions on the escape routes become untenable.
- RSET, required safe egress time — the time people need to reach a place of safety. It includes detection, alarm, the time before people start to move, and travel.
The design is acceptable when ASET exceeds RSET by a margin agreed with the approving authority. Smoke modelling addresses the ASET side. RSET comes from separate evacuation analysis.
Where FDS comes in
FDS, the Fire Dynamics Simulator, is a fire-specific CFD program developed by NIST in the United States. It calculates how smoke and heat from a fire move through a building over time, including the effect of extract fans, vents, doors and make-up air. Its companion program, Smokeview, displays the results. FDS is free and widely accepted by reviewers, and its technical basis and validation are published.
The design fire
The model does not predict what will burn. The fire engineer specifies a design fire: a heat release rate over time that represents a credible severe fire for the space. Growing fires are commonly described by a "t-squared" curve, where heat release rises with the square of time. Standard growth rates are named slow, medium, fast and ultra-fast. The fire may then be capped at a peak size set by the fuel, by ventilation or by sprinkler operation.
The design fire, its location and the amount of soot it produces drive the result more than anything else. They must be agreed and recorded before modelling starts. Several fire locations are normally tested.
Tenability limits
ASET is reached when conditions at head height on the escape route pass an agreed limit. Limits are usually set for:
- Visibility — the distance people can see through smoke. This is usually the first limit to be reached.
- Temperature of the smoke layer and of the air people move through.
- Toxic gases, often assessed through carbon monoxide.
- Radiant heat from the hot layer above.
The values come from the fire engineer and the guidance being followed. They are project inputs, not settings in the software.
Why mesh resolution matters
FDS divides the space into cells. Cells that are too large smear out the fire plume and give misleading smoke temperatures and layer heights. Published guidance relates the cell size to the size of the fire, so a small fire needs a finer mesh than a large one. A sound study includes a mesh sensitivity check: the same case run on a finer mesh to show that the conclusion does not change.
What a good study contains
- A written brief: objectives, scenarios, design fires and acceptance limits, agreed in advance;
- Geometry, openings and smoke control system operation, with timings;
- Time histories of visibility, temperature and gas levels at defined points on the escape routes;
- Sensitivity checks on mesh and on key inputs;
- A clear statement of limitations.
Animations are useful for explaining results. On their own they are not evidence.
What the model cannot do
A fire model covers the scenarios it was given and no others. It does not model how people behave, it does not replace sprinkler or structural design, and it does not certify the building. Everyday airflow and comfort are also a different study with different tools; see CFD versus energy modeling. Details of our scope are on the FDS simulation services page.
The takeaway
ASET against RSET is a simple comparison built on careful inputs. Smoke modelling gives the fire engineer a reasoned estimate of how long escape routes stay usable for an agreed fire. Its value depends on the design fire, the limits, the mesh and honest reporting of what was and was not tested.
Need smoke modelling for a fire strategy?
We provide FDS smoke and heat modelling in support of the appointed fire engineer, with documented inputs, sensitivity checks and reviewable results. Let's talk.
Get in touchThis article is general information and is not fire safety advice. Fire modelling supports, and does not replace, the judgement of a competent fire engineer and the approval of the relevant authority. Design fires, tenability criteria and acceptance are set for each project by those responsible for the fire strategy.