Clients often ask for "a simulation" without knowing there are two very different kinds. A building energy model and a CFD study both run on computers and both produce colourful output, but they answer different questions. Choosing the wrong one wastes money. Choosing the right one early can save a design.
What an energy model does
A building energy model follows the whole building through every hour of a year. It tracks heat flows through the envelope, internal gains, HVAC equipment and controls, and reports annual energy, peak loads, cost and carbon. It is the tool for code compliance, LEED points, system comparison and retrofit planning.
To do a year of calculation in minutes, it makes one large simplification: each zone is a single, perfectly mixed volume of air. A room has one temperature. The model cannot tell you that it is warm near the ceiling, cold at the window or draughty at one desk.
What CFD does
Computational fluid dynamics divides the air in a space into millions of small cells and solves for velocity, temperature and often humidity or contaminants in each one. It shows exactly what the energy model averages away: where air moves, where it stalls and how temperature varies through the space.
The price is time. CFD usually examines one space under one or a few conditions, such as a summer peak afternoon or a winter morning. It is not a tool for annual energy.
When a project needs CFD
- Tall spaces — atria, auditoria and halls, where warm air collects high up and the occupied zone behaves differently from the average.
- Comfort near facades — cold downdraught from tall glazing, or radiant and draught effects that a single zone temperature hides.
- Displacement and underfloor systems — which depend on stratification to work.
- Natural ventilation — checking that air actually crosses the floor plate at the wind and temperature conditions expected.
- Diffuser layout — throw, short-circuiting and dead zones before installation.
- Data centres — hot spots, recirculation and containment.
- Air quality — age of air, CO₂ distribution and contaminant removal.
- Outdoor conditions — pedestrian wind comfort and exhaust dispersion around buildings.
Our CFD simulation services cover these cases. Fire and smoke movement is a separate discipline with its own tools; see smoke modelling for fire safety.
When an energy model is enough
Standard offices, apartments, schools and retail with conventional ceiling-height spaces and mixed-air systems rarely need CFD. The well-mixed assumption is reasonable there, and zone-level comfort checks such as PMV and PPD can be done from the energy model's results.
Using them together
The two tools work best in sequence. The energy model identifies the critical hours and supplies the boundary conditions: surface temperatures, solar gains, internal loads and supply air conditions. CFD then resolves the airflow for those hours. Findings flow back the other way too. If CFD shows strong stratification in an atrium, the energy model can be adjusted so that cooling load is calculated for the occupied zone and not the full height.
A quick test
Ask what the answer will look like. If it is a number per year, such as kWh, cost, carbon or percent savings, the project needs an energy model. If it is a picture of a space, showing where it is too warm, too still or too draughty, the project needs CFD. Many complex buildings need both.
The takeaway
Energy modeling and CFD are complementary. One covers the whole building across time with the detail of the room removed. The other covers one room in full detail at a moment in time. Match the tool to the question, and use the energy model to set up the CFD where both are needed.
Not sure which study you need?
We deliver both whole-building energy models and CFD airflow studies, and can scope the right one for your question. Let's talk.