A furnace delivers the same heat at 40°F as it does at −10°F. An air-source heat pump does not. As the outdoor air gets colder, there is less heat to extract from it, and the heat pump's capacity falls just as the house needs more. Sizing a heat pump in a cold climate is therefore not a single number. It is a question of where two lines cross.

Two lines on one chart

Draw the house's heat loss against outdoor temperature. It is roughly a straight line: zero at around 60 to 65°F, rising to the Manual J heating load at the design temperature. Then draw the heat pump's heating capacity from the manufacturer's data. It slopes the other way, falling as the outdoor temperature drops.

The temperature where the lines cross is the thermal balance point. Above it, the heat pump alone can heat the house. Below it, something else has to make up the difference.

Rated capacity is not design capacity

Heat pumps are sold by nominal tons, which reflect cooling capacity at standard rating conditions. Heating capacity is usually published at 47°F and 17°F, and cold-climate models add 5°F and lower. A unit can lose a large share of its capacity between 47°F and 5°F. Only the manufacturer's expanded performance data for the exact outdoor and indoor unit combination shows how much. Independent lists of cold-climate heat pumps, such as the one published by NEEP, are a useful starting point for comparing models at low temperatures.

Size for cooling or for heating?

This is the central decision, and Manual S sets the rules for it.

In practice, many cold-climate designs use a variable-capacity heat pump sized close to the heating load, with a modest amount of backup heat for the coldest hours.

Backup heat

Below the balance point, supplemental heat covers the shortfall. It is usually electric resistance strips in the air handler, sometimes an existing furnace in a dual-fuel arrangement. Size the backup to cover the gap between the heat loss and the heat pump capacity at the design temperature. Many designers also check that the backup could keep the house above freezing if the heat pump failed, which local code or the client may require.

Control matters as much as size. Backup heat should be staged and locked out above the balance point, so it does not run on mild mornings when the heat pump could manage alone. Resistance heat used unnecessarily wipes out much of the heat pump's efficiency advantage.

Lockout, defrost and duct temperatures

Replacing a furnace

When an existing home moves from a furnace to a heat pump, never size from the old furnace. Furnaces were routinely oversized, often by a large margin. Run a fresh Manual J on the house as it is today, including any insulation, window or air-sealing upgrades. The real heat loss is very often smaller than the old equipment suggests, which may allow a smaller, less expensive heat pump.

The takeaway

Cold-climate heat pump sizing starts with an accurate Manual J and the manufacturer's low-temperature data. Plot the two lines, find the balance point, choose equipment that suits both seasons, and size and control the backup heat so it only runs when it is needed. Our Manual J, S and D services cover this whole process.