Air-Side Economizers: Free Cooling, High-Limit Controls and Code Requirements

Air-side economizer free cooling and high-limit control
When the air outside is cooler than the air being returned, the cheapest chiller is an open damper.

Many commercial buildings need cooling even when it is cool outside. Offices with people, lighting and computers, deep floor plates and interior zones generate heat all year. An air-side economizer takes advantage of this: when the outdoor air is cool enough, it opens the outdoor air damper wide and uses that air to cool the building, reducing or replacing the work of the compressors.

How an economizer works

A normal air handler mixes a minimum amount of outdoor air, set by ventilation requirements, with return air from the building. In economizer mode the outdoor damper opens further, up to 100% outdoor air, and the relief or exhaust path opens to match. The control system then modulates the dampers to reach the desired supply air temperature.

Integrated versus non-integrated

An integrated economizer can run at the same time as mechanical cooling. When outdoor air is cooler than the return air but not cool enough to meet the whole load, the economizer brings in as much outdoor air as it can and the cooling coil finishes the job. A non-integrated economizer must choose one or the other, so it loses the hours when partial free cooling was possible. Current energy codes generally require integrated operation.

High-limit controls

The economizer must also know when to stop. Above a certain point, outdoor air is warmer or more humid than return air, and bringing it in increases the cooling load. The high-limit control makes that decision. Common types are:

In humid climates, dry-bulb-only controls can bring in air that is cool but damp, adding a hidden latent load. For this reason energy codes restrict which high-limit types may be used in each climate zone and set the required setpoints.

Where economizers are required

ASHRAE 90.1 and the IECC require air or water economizers on cooling systems above a capacity threshold in most climate zones, with exceptions for the hottest and most humid zones and for certain system types and uses. Exceptions also exist where other efficiency measures are used instead, such as higher-efficiency cooling equipment. The thresholds and exceptions change between editions, so the requirement has to be checked for each project.

Why many economizers fail in the field

Economizers are mechanical and depend on sensors, and both fail without anyone noticing. Studies of existing rooftop units have repeatedly found a large share of economizers not working as intended. The common problems are:

Codes now often require fault detection on smaller units for this reason. Commissioning and retro-commissioning, such as the work required under NYC Local Law 87, routinely check economizer operation.

Modelling economizers

In EnergyPlus and tools built on it, the economizer is defined in the outdoor air controller: type, high-limit control, setpoints and whether it is integrated. A few points matter for accuracy:

Water-side economizers

Where large outdoor air ducts are impractical, as in tall buildings or data centres, a water-side economizer uses a cooling tower and heat exchanger to make chilled water without running the chiller in cold weather. It achieves a similar result through the water system instead of the air system.

The takeaway

An economizer is one of the cheapest efficiency measures in commercial HVAC, but only if it is integrated, uses a high-limit control suited to the climate, and actually works. Specify it carefully, commission it, check it periodically, and model it as it will really operate.