Many commercial buildings need cooling even when it is cool outside. Offices with people, lighting and computers, deep floor plates and interior zones generate heat all year. An air-side economizer takes advantage of this: when the outdoor air is cool enough, it opens the outdoor air damper wide and uses that air to cool the building, reducing or replacing the work of the compressors.
How an economizer works
A normal air handler mixes a minimum amount of outdoor air, set by ventilation requirements, with return air from the building. In economizer mode the outdoor damper opens further, up to 100% outdoor air, and the relief or exhaust path opens to match. The control system then modulates the dampers to reach the desired supply air temperature.
Integrated versus non-integrated
An integrated economizer can run at the same time as mechanical cooling. When outdoor air is cooler than the return air but not cool enough to meet the whole load, the economizer brings in as much outdoor air as it can and the cooling coil finishes the job. A non-integrated economizer must choose one or the other, so it loses the hours when partial free cooling was possible. Current energy codes generally require integrated operation.
High-limit controls
The economizer must also know when to stop. Above a certain point, outdoor air is warmer or more humid than return air, and bringing it in increases the cooling load. The high-limit control makes that decision. Common types are:
- Fixed dry-bulb — stop above a set outdoor temperature. Simple and reliable, with the setpoint chosen for the climate.
- Differential dry-bulb — stop when outdoor air is warmer than return air.
- Fixed enthalpy — stop above a set outdoor heat content, which accounts for humidity.
- Differential enthalpy — stop when outdoor heat content exceeds that of the return air.
In humid climates, dry-bulb-only controls can bring in air that is cool but damp, adding a hidden latent load. For this reason energy codes restrict which high-limit types may be used in each climate zone and set the required setpoints.
Where economizers are required
ASHRAE 90.1 and the IECC require air or water economizers on cooling systems above a capacity threshold in most climate zones, with exceptions for the hottest and most humid zones and for certain system types and uses. Exceptions also exist where other efficiency measures are used instead, such as higher-efficiency cooling equipment. The thresholds and exceptions change between editions, so the requirement has to be checked for each project.
Why many economizers fail in the field
Economizers are mechanical and depend on sensors, and both fail without anyone noticing. Studies of existing rooftop units have repeatedly found a large share of economizers not working as intended. The common problems are:
- Dampers stuck closed, so free cooling never happens;
- Dampers stuck open, so the building heats and cools far more outdoor air than intended;
- Failed or poorly calibrated temperature and humidity sensors;
- High-limit setpoints left at factory defaults that do not suit the climate;
- Linkages disconnected during maintenance.
Codes now often require fault detection on smaller units for this reason. Commissioning and retro-commissioning, such as the work required under NYC Local Law 87, routinely check economizer operation.
Modelling economizers
In EnergyPlus and tools built on it, the economizer is defined in the outdoor air controller: type, high-limit control, setpoints and whether it is integrated. A few points matter for accuracy:
- The minimum outdoor air must be set correctly, since the economizer adds to it.
- Economizer limits must reflect the actual control, not a generous default.
- In an Appendix G model, the baseline includes or excludes an economizer by climate zone, with a specified high-limit control. The proposed model should show the design.
- Energy recovery and economizers interact. When economizing, the ERV or HRV should be bypassed or slowed.
Water-side economizers
Where large outdoor air ducts are impractical, as in tall buildings or data centres, a water-side economizer uses a cooling tower and heat exchanger to make chilled water without running the chiller in cold weather. It achieves a similar result through the water system instead of the air system.
The takeaway
An economizer is one of the cheapest efficiency measures in commercial HVAC, but only if it is integrated, uses a high-limit control suited to the climate, and actually works. Specify it carefully, commission it, check it periodically, and model it as it will really operate.