Energy Modeling · Inputs · ·8 min read

Weather Files for Energy Modeling: TMY, EPW, AMY and Future Climate

Weather files TMY and EPW for building energy modeling
The building is designed by the team. The weather is chosen by the modeller.

Every hourly energy simulation runs against 8,760 hours of weather. Change the weather file and the results change, sometimes by more than a design measure would. Yet the weather file is often picked in seconds from a drop-down list. It deserves more thought than that.

Typical years

Most compliance and design models use a typical meteorological year (TMY). A TMY is not an average and not a real year. It is built from twelve real months, each chosen from a long record because it is the most representative for that month, then joined together. The result keeps realistic hour-to-hour swings while representing long-term conditions.

Because the climate has warmed, a typical year built from older records tends to show more heating and less cooling than one built from recent records. For the same city the difference can be several percent of annual energy.

The EPW format

EnergyPlus and most tools based on it read EPW files. An EPW holds one line per hour with dry-bulb and dew-point temperature, humidity, pressure, solar radiation (global, direct and diffuse), wind speed and direction, and sky cover, plus a header with location, elevation and ground temperatures. Solar radiation is frequently modelled from cloud cover instead of measured, so it is the least certain column in many files.

Design days are a separate thing

A weather file is for annual energy. Equipment sizing uses design days: short, severe conditions taken from ASHRAE climatic design data, such as the 99.6% heating and 0.4% or 1% cooling conditions. A typical year by definition avoids extremes, so sizing from it gives undersized equipment. A mismatch between design days and the weather file is also a common cause of unmet load hours.

Actual years for calibration

When a model is compared with utility bills, typical weather is the wrong input. The bills were produced by the weather of a real year. Actual meteorological year (AMY) files for the billing period are needed for calibration under ASHRAE Guideline 14 and for existing-building retrofit models. Once calibrated, the model is often rerun with a typical year to report normalised savings.

Future climate and extreme years

A building completed today will operate into the 2070s. Future weather files shift present-day files using climate model projections, so a design can be tested against the conditions it will meet later. They are most useful for overheating risk, cooling plant sizing and passive design. The UK already requires this approach for overheating assessments, using design summer years.

Choosing a file

The takeaway

The weather file is a design input like any other. Use a typical year for compliance and design comparisons, design days for sizing, an actual year for calibration, and future files to test resilience. Then record which one was used and why.

Need a model run on the right weather?

We select and document weather data for compliance models, calibrate existing-building models to actual-year weather, and test designs against future climate files. Let's talk.

Get in touch