A growing number of building departments ask for Manual J, Manual S and Manual D reports with residential mechanical permits. Many submissions come back with comments. The cause is rarely a wrong calculation. It is usually that the reports do not match the drawings, or do not match each other. Knowing what a reviewer looks for makes the first submission the last.
1. Project information and design conditions
The first page should state the address, the climate data location used, the outdoor design temperatures for heating and cooling, and the indoor conditions. Reviewers check these first because they are easy to verify. Common indoor conditions are 70°F for heating and 75°F with 50% relative humidity for cooling. Outdoor values should match the published design data for the location. Inflated outdoor temperatures are the quickest sign of a padded calculation.
2. Construction and window inputs
This section lists every wall, roof, floor, door and window type with its U-factor or construction. Reviewers compare it with the building plans and with the energy code compliance report:
- Insulation R-values should match the wall sections and the REScheck or performance path report.
- Window U-factor and SHGC should match the window schedule.
- Window and wall areas should be close to those on the drawings.
- Infiltration should reflect the code's air leakage target or a test result, not a "loose" default for a new home.
- Duct location and insulation should match the mechanical plan.
3. Room-by-room loads
The heating and cooling load of every room, with sensible and latent cooling, and the whole-house totals. Room names should match the floor plan. Reviewers look for missing rooms, rooms that are clearly unrealistic, and an orientation that matches the site plan. If the house might be built facing several directions, as with builder plans, the report should say which orientation was used or show the worst case.
4. Manual S equipment selection
The equipment check should name the actual outdoor and indoor unit models and show their capacity at the design conditions, taken from the manufacturer's data. It then compares total, sensible and latent cooling capacity, and heating capacity, against the Manual J loads and the Manual S sizing limits. For heat pumps it should show the balance point and the backup heat; see cold-climate heat pump sizing. A generic "3-ton" entry with no model number is a common reason for comments.
5. Manual D duct design
Where required, the duct report shows the design airflow, the blower's available static pressure, the component pressure losses, the total effective length, the design friction rate, and the size and airflow of each duct run. It is usually accompanied by a duct layout drawn on the floor plan. Reviewers check that the room airflows follow the room loads and that the total airflow matches the selected equipment.
The inconsistencies that cause most rejections
- Different floor areas or room lists in the Manual J and on the plans;
- Insulation values that differ between the Manual J and the energy code report;
- Equipment in Manual S that differs from the equipment on the mechanical drawings;
- Airflow in Manual D that does not match the equipment selected in Manual S;
- Design conditions for the wrong city or an unexplained safety margin;
- Missing signatures or contractor information where the jurisdiction requires them.
A quick self-check before submitting
Lay the reports beside the drawings and confirm five things: the same address and orientation, the same areas, the same insulation and windows, the same equipment model, and airflow that agrees between Manual S and Manual D. A set that passes those checks is in good shape for review.
The takeaway
A permit reviewer reads Manual J, S and D as one story about one house. Make every page agree with the drawings and with the other reports, use published design conditions and real equipment data, and the review becomes a formality. Our Manual J, S and D services produce the full set, consistent with the energy code report.
Need a permit-ready Manual J, S and D set?
We prepare ACCA Manual J, S and D calculations in Wrightsoft Right-Suite Universal for new homes, additions, ADUs and heat pump replacements across the US. See our residential HVAC design services or get in touch.
Get in touchThis article is general guidance and reflects information available at the time of writing. Submission requirements are set by each building department and by the code edition it has adopted — always confirm local requirements before submitting.